VigiPacT RH99M is a DIN rail mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 380/415VAC 50/60Hz. The operational supply voltage is 380/415VAC 50/60Hz. The operational supply voltage is 380/415VAC 50/60Hz. The current sensitivity (IDn) is selectable with 9 thresholds from 30mA to 30A. The time delay (Dt) is selectable with 9 settings from instantaneous to 4.5s. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000VAC 50/60/400Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.
Range : VigiPacT
Device short name : RH99M
Product or component type : Residual current protection relay
relay application : Protection relay
mounting support : DIN rail
Earth-leakage protection class : Type A
Type of setting : Selector
Residual earth-leakage sensitity adjustment type : Adjustable 9 settings
Earth-leakage sensitivity : 0.03…30 A
Earth-leakage time delay :
- Instantaneous for 0.03 A
- Adjustable 9 settings 0…4.5 s for 0.03…30 A
Current sensors compatibility :
- VigiPacT TOA earth leakage current sensor
- VigiPacT A earth leakage current sensor
- VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current : 8 A
Minimum load : 10 mA at 12 V
[Us] rated supply voltage : 380...415 V AC 50/60 Hz 55...110 %
Power consumption in VA: 4 VA
Monitored distribution system :
- 1000 V - AC at 50/60 Hz (maximum)
- 1000 V - AC at 400 Hz (maximum)
Earthing system :
[Uimp] rated impulse withstand voltage : 8 kV
Reset : Manual reset
Test function :
Monitoring :
- Electronics (continuous)
- Power supply (continuous)
- Relay/sensor link (continuous)
Type of measurement : Earth fault current internal measurement, range: 80...100 %
Tamperproof of settings : Protected by sealable cover
Connections - terminals :
- Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
- Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
- Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
- Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
- Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
- Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
- Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
- Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
- Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
- Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
- Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
- Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
- Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
- Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
- Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Wire stripping length :
- Auxiliary power supply: 7 mm for top connection
- Fault: 8 mm for bottom connection
- Relay test and fault reset: 5 mm for bottom connection
- Sensor: 5 mm for top connection
- Voltage presence: 8 mm for bottom connection
Tightening torque :
- Auxiliary power supply: 0.6 N.m top
- Fault: 0.6 N.m bottom
- Relay test and fault reset: 0.25 N.m bottom
- Sensor: 0.25 N.m top
- Voltage presence: 0.6 N.m bottom
9 mm pitches : 6
Standards :
- EN/IEC 60947-2 Annex M
- EN/IEC 60755
- UL 1053
- CAN/CSA C22.2 No. 144
Width : 54 mm
height : 81 mm
Depth : 74 mm
Net weight : 0.3 kg
IP degree of protection :
- IP40 on front face: conforming to EN/IEC 60529
- IP30 on side parts: conforming to EN/IEC 60529
- IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection : IK07 conforming to EN 50102
Mechanical robustness :
- Fire resistance conforming to IEC 60695-2-1
- IK protection 2 joules: IK07 conforming to EN 50102
- Vibrations 13.2...100 Hz: 0.7 g
- Vibrations 2...13.2 Hz: +/- 1 mm
Overvoltage category : IV
Electrical shock protection class : Class II
Electromagnetic compatibility :
- Conducted and radiated emissions: , B, conforming to CISPR 11
- Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6
- Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2
- High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5
- Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4
- Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity : 95 % at 55 °C
Pollution degree : 3 conforming to IEC 60664-1
Ambient air temperature for operation : -35…70 °C
Ambient air temperature for storage : -55…85 °C